Roofing
Roof Vent / Ventilation Calculator
Roof vents by the IRC 1:300 and 1:150 attic-area rule on the US side and the BS 5250 eaves and ridge openings on the metric side, from your vent's net free area
Updated October 10, 2026 · Live
What this tool does
Sizes cold-roof ventilation two ways. On the US side it applies IRC R806.2: attic floor area divided by 300 or 150, split half high and half low, in vents of the net free area you enter. On the metric side it applies the BS 5250 cold pitched roof openings: 10 mm continuous at the eaves at 15° and over, 25 mm below, in tile vents, with the 5 mm ridge opening flagged for pitches over 35° or spans of 10 m or more. Figures in both unit systems.
US: attic area over 300 or 150, half high and half low. Metric: eaves length times 10,000 or 25,000 mm² per metre, in tile vents.
People also use
Formula Used
Formula Used
How the roof vent / ventilation calculator works
Roof ventilation is sized two ways, and the calculator does whichever your side of the unit switch uses. On the US side it follows the International Residential Code, as published on UpCodes (Virginia IRC 2021, R806.2): "the minimum net free ventilating area shall be 1/150 of the area of the vented space", or 1/300 where "not less than 40 percent and not more than 50 percent of the required ventilating area is provided by ventilators located in the upper portion of the attic", within 3 ft (914 mm) of the ridge, with the balance "in the bottom one-third of the attic space", and, in climate zones 6 to 8, a Class I or II vapour retarder on the warm side of the ceiling. The calculator takes the attic floor area, divides by the ratio you choose, splits the result half high and half low, and divides each half by the net free area of one vent. On the metric side it follows BS 5250, the British code of practice for condensation control that Approved Document C points to: a cold pitched roof gets a continuous eaves opening equivalent to 10 mm at pitches of 15° and over, 25 mm below 15°, and a further 5 mm at the ridge where the pitch exceeds 35° or the span is 10 m or more. That is 10,000 or 25,000 mm² per metre of eaves and 5,000 mm² per metre of ridge, and the calculator divides the eaves figure by the free area of one tile vent.
The US default is a 1,200 ft² (111.5 m²) attic at 1:300: 576 in² (4.00 ft², 0.37 m²) of net free area, 288 in² high and 288 in² low. Entered as 18 in² units, which is one foot of the ridge vent Air Vent's ICC-ES report ESR-2071 rates at "18 square inches per lineal foot (3806 cm²/m)", that is 16 ft of ridge vent and the same net free area again in soffit vents, 32 units in all. At 1:150 everything doubles. The metric default is 20 m (65.6 ft) of eaves on a 25° roof with an 8 m span: 200,000 mm² (310 in²) of eaves opening, which a 10,000 mm² tile vent, the free airflow Manthorpe's double roman tile vent data sheet gives "per unit", meets at one vent per metre, 20 vents, and no ridge ventilation because the pitch and span are under the thresholds. At 10° the opening is 25 mm, 500,000 mm², and the same vents go in every 0.4 m.
Typical US roofing wastage
Vents are not wasted; they are rounded. Both methods round up to whole vents on each side, so a count that comes out at 15.2 becomes 16, and on the US side the two halves are rounded separately so that the high and low sides each carry at least their share. Where the vent is a continuous product, a ridge vent or a soffit strip sold by the foot or the metre, enter its net free area per foot or per metre as the "vent" and read the count as feet or metres of product, then round up to the lengths it is sold in: the ridge vent above comes in 4 ft pieces, so 16 ft is four pieces. Where the vent is a unit, a roof louver, a gable vent or a tile vent, the count is the units.
The free area is the figure that matters and it is never the hole size. A 10,000 mm² tile vent has a face far larger than 10,000 mm²; the grille, the baffles and the weather path take the rest, and the maker's data sheet gives the net figure. Wienerberger's roof space ventilation note (UK) puts the conversion plainly: "a continuous gap of 10mm gives 10,000mm² per metre run. Tile vents with a free vent area of 10,000mm² spaced at 1 metre intervals will provide this", and for the ridge, "a continuous gap of 5mm gives 5,000mm² per metre run", which the same vents provide at 2 m intervals. US products carry a net free area in square inches on the label or in their evaluation report.
What this tool does not do
It sizes a cold roof, one with the insulation on the ceiling and a ventilated space above. It does not design a warm roof or an unvented attic, which the IRC allows under R806.5 with the insulation against the sheathing and no ventilation at all, nor the vapour-permeable-underlay roofs that UK practice ventilates at lower rates with the underlay doing part of the work. It does not check the airflow path: the IRC asks for at least a 1 in (25 mm) gap between insulation and sheathing at the eaves, and a tile vent above a blocked eave ventilates nothing. It does not place the vents, and it does not price ridge or soffit products sold by length.
On-site considerations for roof vent / ventilation
Balance is the point of both rules. Air comes in low and goes out high, so the eaves and the ridge need each other: on the US side the 1:300 allowance exists because a high-and-low split moves more air than the same area all in one place, and on the UK side the ridge 5 mm is added on steep or wide roofs because the eaves alone cannot flush the apex. Eaves vents need the insulation held back so the opening is not stuffed with it, which is what over-fascia and rafter-tray products do, and tile vents need to sit in a course above the insulation line with their chute clear of the underlay. On the US side, the openings must be screened or sized between 1/16 in and 1/4 in (1.6 to 6.4 mm), per R806.1, to keep out birds, rodents and insects.
Codes and compliance
The two rules are jurisdiction-specific and are quoted as such. The IRC applies in the United States as adopted by each state; the figures here are from Virginia's adoption of the 2021 edition, and the vapour-retarder condition only bites in climate zones 6 to 8. In England, Approved Document C (2013 edition) says at paragraph 6.10 that a roof meets the interstitial-condensation requirement if designed and constructed to BS 5250 and BS EN ISO 13788, and at 6.11 that the requirement is met "by the ventilation of cold deck roofs"; the 10 mm, 25 mm and 5 mm figures are BS 5250's, carried into NHBC Standards and manufacturers' guidance. Scotland, Wales and Northern Ireland have their own technical documents.
Before you order
The order is the vent count on each side, plus the lengths for anything continuous, and the thing to check first is the net free area on the product you are buying, because a count made with one maker's figure does not transfer to another's. On the US side, the high half can be a ridge vent by the foot or roof louvers by the unit, and the low half soffit vents by the foot or the panel; the calculator gives both halves in the same unit, so it is run once for each product. On the UK side, tile vents are matched to the tile profile, double roman, pantile, plain or slate, and a plain-tile vent carries a smaller free area, 7,000 mm² on the Manthorpe range, so the count goes up.
Adjusting the defaults
Every input is editable. On the US side: the attic floor area in square feet, the ratio, 1:300 where the high-and-low split and any vapour retarder are in place and 1:150 otherwise, the net free area of one vent or one foot of vent in square inches, and a price. On the metric side: the total eaves length in metres, the roof pitch in degrees, the span in metres, which decides the ridge rule with the pitch, the free area of one tile vent in square millimetres, and a price. Leave the price at zero to see the count only.
Using this roof vent / ventilation calculator alongside other BuildMetricLab tools
Find the eaves and ridge lengths with the roof area calculator, the pitch with the roof pitch calculator, and the soffit the low vents sit in with the soffit and fascia calculator. All BuildMetricLab tools run in your browser with no sign-up, and the formula is on the page so the maths can be checked.
Sources & methodology
US side (IRC R806.2): net free area = attic floor area ÷ ratio, where the ratio is 150, or 300 where 40 to 50% of the area is provided high (within 3 ft of the ridge) and the rest low; the calculator splits the area 50/50 and rounds each half up to whole vents of the entered net free area. Inputs in ft² and in² are converted to m² and mm² first (1 in² = 645.16 mm²). Metric side (BS 5250, as applied in Approved Document C, NHBC Standards and manufacturers' guidance): eaves opening = eaves length × 10,000 mm²/m for pitches of 15° and over (a continuous 10 mm gap) or 25,000 mm²/m below 15° (25 mm); vents = eaves opening ÷ free area of one vent, rounded up; ridge ventilation of 5,000 mm²/m (5 mm) is flagged where the pitch exceeds 35° or the span is 10 m or more. Product figures: Manthorpe tile vents 10,000 mm² free airflow per unit (7,000 mm² for the plain-tile pattern); Air Vent ShingleVent II 18 in² per lineal foot (3,806 cm²/m).
- UpCodes, International Residential Code 2021 (Virginia adoption), R806 Roof ventilation: R806.1 screened openings 1/16 to 1/4 in; R806.2 minimum net free ventilating area 1/150 of the vented space, or 1/300 with 40 to 50% high and a Class I or II vapour retarder in climate zones 6 to 8; R806.3 1 in clearance at the eaves; R806.5 unvented assemblies
- GOV.UK, Approved Document C (England, 2013 edition), paragraphs 6.10 and 6.11: roofs designed to BS 5250 and BS EN ISO 13788 meet the interstitial condensation requirement; ventilation of cold deck roofs
- Wienerberger, Roof space ventilation technical note (UK, to BS 5250): a continuous 10 mm gap is 10,000 mm² per metre, met by 10,000 mm² tile vents at 1 m intervals; a 5 mm gap is 5,000 mm² per metre; 10 mm eaves below 35° and under 10 m span, 5 mm ridge added over 35° or over 10 m
- Manthorpe Building Products, double roman tile vent product information sheet: free airflow 10,000 mm² per unit, 4 mm grille openings
- ICC Evaluation Service, ESR-2071, Air Vent ShingleVent II ridge vent (reissued 2026): net free ventilation area 18 square inches per lineal foot (3,806 cm²/m)
Frequently asked questions
Are roof vent / ventilation calculator results accurate enough to order materials?
Yes, if the net free area entered is the figure on the data sheet of the vent you will buy, because that is the only number that varies between products. On the US side, check that the high and low halves are placed as the 1:300 rule requires before using that ratio; on the UK side, check that the vents will sit above the insulation line with a clear path. Continuous products are ordered in their stock lengths, so the count in feet or metres is rounded up to pieces.
How is the number of vents calculated?
On the US side, the attic floor area is divided by 150, or by 300 where 40 to 50% of the area is high and the rest low, which is the IRC R806.2 rule; the result is split in half, and each half is divided by the net free area of one vent and rounded up. On the UK side, the eaves length is multiplied by 10,000 mm² per metre at pitches of 15° and over, or 25,000 mm² below, which is the BS 5250 continuous 10 mm or 25 mm opening, and divided by the free area of one tile vent; a 5 mm ridge opening is flagged where the pitch exceeds 35° or the span is 10 m or more.
Is this tool a substitute for professional advice?
No. It sizes the opening area. Whether the roof should be ventilated at all or built as an unvented or warm roof, where the vents go, whether the insulation leaves the airway open, and which rule applies in your jurisdiction are matters for the designer and the building control body or building department. For work that affects structure, gas, electrics, plumbing or drainage to a public sewer, use a suitably qualified professional.
Can I change the unit prices?
Yes. The price per vent is an input; enter the price of one vent, or of one foot or one metre of a continuous product if that is how you entered the free area, and the cost is the count times that price. Leave it at zero to see the count only.
Spotted something off?
Calculations or display — let us know.