Air Sealing / Weatherstripping Calculator
Heating saved by air sealing, from before-and-after blower door ACH50 figures, in metric or US units
Updated October 8, 2026 · Live
What this tool does
Turns a blower door result before and after air sealing into the heat and money saved each year. It converts ACH50 to natural infiltration with the leakage-infiltration ratio (ACH50 ÷ N), applies the 0.33 W per m³/h per K ventilation heat-loss constant to the heated volume and temperature difference, then multiplies by the heating hours, divides by the system efficiency and prices the fuel at your rate.
ACH50 ÷ N gives the real air change; the cut in air change times volume, 0.33 and the temperature difference gives the watts; hours, efficiency and price turn that into money.
People also use
Formula Used
Formula Used
How the air sealing calculator works
A blower door test gives one number for a house: the air changes per hour at 50 pascals, ACH50. Seal the leaks and test again, and the drop between the two figures is what this calculator turns into heating money. It takes the heated volume (floor length, width, ceiling height and the number of storeys the test covered), the ACH50 before and after, the average indoor-outdoor temperature difference over the heating season, the hours the heating runs, the efficiency of the heating system and what a kilowatt-hour of its fuel costs. Out come the natural air change before and after, the airflow you have stopped, the heat load that goes with it, the heat and fuel saved over a year, and the saving in money.
The step most online tools skip is the first one. ACH50 is a test condition, not how the house breathes on an ordinary day; a fan is pulling 50 Pa, which is a strong gale. Average infiltration through the year is far lower. Max Sherman's 1987 paper at Lawrence Berkeley Laboratory, Estimation of infiltration from leakage and climate indicators, writes the relationship as ACH = ACH50 ÷ N, where N is the leakage-infiltration ratio, and the rule of thumb is N = 20. A house that tests at 8 ACH50 is really changing its air about 0.4 times an hour. Feed 8 straight into a heat-loss formula and the answer is twenty times too big, which is the mistake this calculator used to make and no longer does.
Twenty is a national average, not a constant. The NIST review of leakage-infiltration ratios by Jones, Persily and Sherman calls it the rule-of-20, the Kronvall-Persily rule or Sherman's ratio, and says plainly that the value "is not applicable to all buildings and climates" and moves with building height, shielding, the size of the leaks and the climate. Sherman's own correction tables scale the base ratio by 0.8 for a two-storey house and 0.7 for three, by 0.9 for an exposed site and 1.2 for a well-shielded one, and the base ratio itself is lower in cold, windy climates than mild ones. The N input is there so you can move it: a tall house on a windy hill in a cold winter sits nearer 15, a sheltered bungalow in a mild climate nearer 25 or 30. The UK's SAP 10.2 energy rating procedure uses the same shortcut for the metric test figure, dividing the air permeability at 50 Pa by 20 to get the infiltration rate.
0.33 watts per cubic metre per hour per degree
Once you have the air actually moving through the house, the heat it carries out is a textbook sum. Air holds about 1,200 joules per cubic metre per kelvin (density around 1.2 kg/m³ times a specific heat of 1,000 J/kg·K); divide by 3,600 seconds and one cubic metre per hour of air warmed by one degree costs 0.33 W. That is the figure in SAP 10.2, where the ventilation heat loss is 0.33 × n × V watts per kelvin, with n the air change rate and V the volume. The calculator multiplies the air change you have stopped by the volume, by 0.33 and by the temperature difference to get a heat load in watts, then by the heating hours to get kilowatt-hours a year. In US units the same constant works out at about 1.06 Btu/h per cubic foot per minute per °F, which is where the familiar 1.08 × cfm × ΔT sensible-heat formula comes from. The page shows the load in watts and Btu/h and the flow in m³/h and cfm whichever side of the unit switch you are on.
Heat saved is not fuel saved. A condensing gas furnace or boiler turns about 90% of the gas into heat in the house, an older one nearer 80%, electric resistance all of it, and a heat pump delivers two and a half to four units of heat per unit of electricity, so its efficiency goes in as 250 to 400%. The fuel row divides the heat by that figure, and the saving is the fuel multiplied by the price you pay for a kilowatt-hour of it. Gas billed by the therm converts at 29.3 kWh a therm.
Two worked examples
A two-storey house with a 40 ft by 25 ft footprint and 8 ft ceilings holds 16,000 ft³ (453 m³). It tests at 8 ACH50 and, after a weekend with caulk, foam and weatherstrip, at 3. With N at 20 the natural air change falls from 0.40 to 0.15, a cut of 0.25 air changes an hour, which on 16,000 ft³ is 66.7 cfm (113 m³/h). At an average 22°F (12.2 K) between inside and out that is 457 W, or 1,559 Btu/h, of heat no longer leaving. Over 2,000 heating hours it is 914 kWh of heat; through a 90% furnace, 1,015 kWh of gas; at $0.12 a kWh, $121.83 a year. The same house taken as a single 16 ft by 13 ft room with the same ACH figures gives $12.67, which is why the volume has to be the whole tested house, not the room you happen to be sitting in.
The metric default is a 10 m by 7 m two-storey house with 2.4 m ceilings, 336 m³. The same 8 to 3 ACH50 drop over N 20 stops 84 m³/h (49 cfm); at 12 K that is 333 W (1,135 Btu/h), 665 kWh of heat over 2,000 hours, 739 kWh of gas through a 90% boiler and, at £0.07 a kWh, £51.74 a year. Change the divisor to 15 for an exposed site and every figure after the volume grows by a third; change the heating to a heat pump at 300% and the fuel row drops to a third.
Where the test limits sit
Codes write their airtightness rules in the same 50 Pa units, which is handy for picking a target. The 2021 International Energy Conservation Code, as carried into the International Residential Code, caps new homes at 5.0 ACH50 in climate zones 0 to 2 and 3.0 ACH50 in zones 3 to 8, tested to ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827. The Virginia adoption of IRC 2021 chapter 11 linked here keeps 5 across the board, so check your own state's table. In England, Approved Document L, Volume 1 sets the limiting air permeability for a new dwelling at 8.0 m³/(h·m²) at 50 Pa in Table 3.1. That is leakage per square metre of envelope, not per volume of house; to compare it with ACH50, multiply by the envelope area and divide by the internal volume, and for an ordinary two-storey house the two numbers come out within a few points of each other. Existing houses are a different matter. A pre-1980 house with a suspended timber floor, open fireplaces and original windows commonly tests at 10 to 15 ACH50 or more, and that is where sealing pays.
Finding the leaks
The money is in the big holes, not the window edges. The US Department of Energy's Consumer Guide to Air Sealing the Home maps nineteen places a house leaks and most of them are out of sight: the top plates of interior walls where they meet the attic, plumbing and wiring penetrations, the chase around the chimney, recessed lights, the attic hatch, the rim joist in the basement or crawl space, and duct joints. Caulk and expanding foam do the small gaps, rigid board and foam the large ones, weatherstrip the doors and sashes. The guide's advice on sequence is the right one: have the house tested, seal the attic and the lowest level first because the stack effect drives air in at the bottom and out at the top, then retest. A blower door with a smoke pencil finds in an hour what a torch and a draught-sensitive hand will not.
Tight has a price, which is why the NIST paper quotes the Swedish motto from the 1970s: build tight, ventilate right. Below about 3 ACH50 a house needs planned ventilation, whether trickle vents, extract fans on a timer or a heat-recovery unit, and any open-flued boiler, stove or water heater needs its combustion air checked by whoever is qualified to do that where you live. The calculator does not subtract the heat that added ventilation will cost; that is a design decision, not an arithmetic one.
What the calculator leaves out
It counts heating only. Cooling savings in a hot climate are real but depend on humidity as much as temperature, so they are not estimated here. It credits nothing for comfort, draughts, dust, noise or the moisture that stops condensing in the roof, which for many owners are the reasons to seal. It assumes the temperature difference you enter is the average over the hours you enter; heating degree-days from a local weather service, multiplied by 24 and divided by the heating hours, give that average. It assumes the heating system efficiency does not change, and it treats the saving as linear in the ACH50 drop, which the leakage-infiltration model is, but the real house is not quite. And it has no way of knowing whether the second blower door number is achievable: halving a leaky house with DIY sealing is a good outcome; getting to 3 ACH50 is a thorough job with the ceiling plane and the floor opened up.
Using this with other BuildMetricLab tools
Sealing and insulating are different jobs that pay for each other. The attic insulation calculator and the wall insulation cost calculator size the insulation that goes on once the air barrier is continuous, the spray foam calculator covers the one material that does both at once, and the window savings calculator prices the glazing that usually comes last. All BuildMetricLab tools run in your browser with no sign-up, and the formula is on the page so the maths can be checked.
Sources & methodology
Natural infiltration = ACH50 ÷ N, where N is the leakage-infiltration ratio (20 by default; Sherman 1987, NIST review by Jones, Persily and Sherman; SAP 10.2 divides the 50 Pa figure by 20). Heated volume V = length × width × ceiling height × storeys. Infiltration cut (m³/h) = (ACH50 before − ACH50 after) ÷ N × V. Heat load reduction (W) = infiltration cut × 0.33 × ΔT, where 0.33 W per m³/h per K is the volumetric heat capacity of air (1,200 J/m³K ÷ 3,600; SAP 10.2 worksheet line 38, 0.33 × n × V). Heat saved (kWh/yr) = watts × heating hours ÷ 1,000; fuel saved = heat saved ÷ system efficiency; saving = fuel saved × price per kWh. US inputs are converted first: ft³ ÷ 35.315 to m³ and °F difference × 5/9 to K; 1 m³/h = 0.5886 cfm and 1 W = 3.412 Btu/h for the displayed equivalents. Heating only; no cooling, comfort or added-ventilation effects.
- Sherman, M. H. (1987), Estimation of infiltration from leakage and climate indicators, Energy and Buildings 10, 81 to 86 (Lawrence Berkeley Laboratory): ACH = ACH50 ÷ N, height and shielding correction factors
- Jones, Persily and Sherman, The origin and application of leakage-infiltration ratios (NIST): the rule-of-20 and when it does not apply
- BRE, SAP 10.2 (2022), The Government's Standard Assessment Procedure for Energy Rating of Dwellings: ventilation heat loss 0.33 × n × V (worksheet line 38); air permeability at 50 Pa ÷ 20 (line 18)
- GOV.UK: Approved Document L, Volume 1 Dwellings (England), Table 3.1 limiting air permeability 8.0 m³/(h·m²) at 50 Pa for new dwellings
- UpCodes: International Residential Code 2021 (Virginia adoption), N1102.4.1.2 air leakage testing at 50 Pa to ANSI/RESNET/ICC 380, ASTM E779 or ASTM E1827 (model code: 5 ACH50 in climate zones 0 to 2, 3 ACH50 in zones 3 to 8)
- US Department of Energy, Energy Saver: Consumer Guide to Air Sealing the Home (2021): the 19 leak locations, materials and sequence
Frequently asked questions
Are air sealing / weatherstripping calculator results accurate enough to order materials?
It estimates a heating saving, not a quantity of caulk or weatherstrip, so there is nothing to order from it. The saving is only as good as the two ACH50 figures and the divisor: a blower door test before and after is the real measure, and N is a climate-and-building average that can be off by a third either way. Treat the result as the order of magnitude for deciding whether a sealing job pays, not as a figure to put in a quotation.
What wastage percentage should I use?
None. This calculator has no wastage input because it estimates energy rather than materials. Its inputs are the heated volume (floor length, width, ceiling height and storeys), the ACH50 before and after sealing, the divisor that turns ACH50 into natural infiltration (20 by default), the average indoor-outdoor temperature difference over the heating season, the heating hours, the system efficiency and the fuel price per kWh. Without a blower door test, 10 to 15 ACH50 is a fair guess for an older house and 5 to 8 for one built in the last few decades.
Does this replace professional advice?
No. It is a planning estimate. Sealing a house also changes how it breathes: open-flued boilers, stoves and water heaters need combustion air, and a house tightened below about 3 ACH50 needs planned ventilation. Have a certified energy assessor test the house and check the ventilation and combustion safety, and use a qualified professional for anything that touches structure, gas, electrics or drainage.
Can I change the unit prices?
Yes. The fuel price per kWh and the system efficiency are both yours to set. Use the unit rate from a bill: electricity directly, gas billed per therm divided by 29.3, oil or LPG from the energy content on the delivery note. Enter a heat pump's coefficient of performance as a percentage, so a COP of 3 is 300%.