Heat Pump Sizing Calculator

Indicative heat pump size in kW, BTU/h and tons from floor area and fabric

Updated July 12, 2026 · Live

What this tool does

Gives an indicative heat pump size in kW, BTU/h and tons from floor area, ceiling height, fabric standard and the design temperature difference.

Enter floor area, ceiling height, a fabric standard and the design temperature difference; the calculator returns an indicative heat pump size in kW, BTU/h and tons.

Inputs
ft²
ft
°F
Result

Indicative Heat Pump Size

5.4 kW

In US Units
18,465 BTU/h (1.5 tons)
Heated Volume
8,000 ft³ (227 m³)
Fabric Standard
Average (typical existing home)
Design Temperature Difference
43 °F (24 °C)
Sizing Basis
Whole-building rule of thumb — a room-by-room heat-loss calculation (MCS in the UK, ACCA Manual J in the US) is the design standard
Plain Estimate
From BrightScale Labs
Invoice maker
Quote at the door. Signed on the spot.
Estimates and invoices for trades, built while you are still in the room.
Scan to get
Get it onGoogle Play

People also use

Formula Used
Q=V⋅f⋅ΔT1000Q = \dfrac{V\cdot f\cdot \Delta T}{1000}
QQ
Indicative heat loss and heat pump size (kW)
VV
Heated volume = floor area × ceiling height
ff
Heat-loss factor (W/m³·°C)
ΔT\Delta T
Design temperature difference

How the heat pump sizing works

A heat pump has to supply as much heat as the building loses on the coldest design day. This calculator estimates that loss with a rule of thumb: the heated volume (floor area × ceiling height) times a heat-loss factor for the fabric, times the design temperature difference, divided by 1,000 to give kW. The formula is Q = V × f × ΔT ÷ 1,000. The factor falls as insulation improves, so a well-sealed home needs a much smaller heat pump than a draughty one of the same size. The page works in ft², ft and °F and converts internally, so the metric and US-unit versions agree.

Example with the defaults on this page: a 1,000 ft² home with 8 ft ceilings has a volume of 8,000 ft³, which is 226.5 m³. At average fabric (1.0) and a 43 °F (23.9 °C) temperature difference the heat loss is 226.5 × 1.0 × 23.9 ÷ 1,000 = 5.4 kW. That is 18,551 BTU/h, or 1.5 tons.

Fabric changes the answer a lot. The same house with poor fabric (1.5) needs 8.1 kW, with good fabric (0.6) 3.2 kW and with passive fabric (0.35) 1.9 kW. Climate changes it too: in a cold climate with a 70 °F (38.9 °C) difference, the average house needs 226.5 × 1.0 × 38.9 ÷ 1,000 = 8.8 kW, which is 30,060 BTU/h or 2.5 tons.

What you enter

Four numbers drive the result. The floor area is the heated area only, so leave out an unheated garage or loft. The ceiling height is the average, because a tall hall or vaulted room adds volume. The fabric standard picks the heat-loss factor: poor for solid walls and single glazing, average for a typical existing home, good for a well-insulated home with double glazing and draught-sealing, and passive for near-Passivhaus fabric. The design temperature difference is the indoor target minus the coldest outdoor design temperature.

Take the winter design temperature for your location from your contractor or a design-conditions table, which gives a temperature that is exceeded about 99% of the time. For 70 °F indoors and a design temperature of 27 °F, the difference is 43 °F. Colder northern climates can give 70 °F or more. Enter a difference, not an absolute temperature. All four fields are checked, so a blank or zero value is refused instead of guessed.

Reading the result

The kW figure is the design heat loss, which is the heat output a heat pump needs at the coldest design condition. It is a first-pass size to sense-check quotes, not a design. A ton of heating or cooling is 12,000 BTU/h, which is 3.52 kW. A result of 5.4 kW is therefore about 1.5 tons.

A sanity check is the heat loss per floor area. The 5.2 kW default on 90 m² is about 58 W/m² (5.4 W/ft²), which is plausible for an existing home. The passive factor gives about 20 W/m² at the default, which is more conservative than the Passivhaus peak heating load criterion of 10 W/m², so a very well-built home may need less. If a quote is far above the tool, ask the installer for the room-by-room calculation. A heat pump much larger than the load can cycle on and off, and ENERGY STAR notes that a system that is too large or too small struggles to meet comfort needs.

Safe by design

This calculator does the arithmetic of sizing. It deliberately stops at the line a certified installer must sign off. It will never tell you a cable or fuse size, an earthing arrangement, a refrigerant charge or a flow temperature, because those are regulated design decisions where a wrong number causes fire, electrocution or equipment failure. All electrical and refrigerant work must be carried out by a qualified, certified installer, and this page is not an installation guide.

Assumptions and limits

This is a whole-building rule of thumb. In the United States, ACCA Manual J is the standard residential load calculation, and ENERGY STAR advises that a contractor verify the size with it. That calculation accounts for each wall, window, floor, roof and air-change rate, which a single factor cannot. The factors used here are 1.5, 1.0, 0.6 and 0.35 W per m³ per °C. They are rule-of-thumb values, so your own building can fall outside them.

The result is the heat to deliver, not the size of the unit to buy. The output of an air-source heat pump falls as the outdoor temperature drops, so the model you choose must meet the design heat loss at your design temperature, not at its rated test condition. The tool also leaves out domestic hot water, which adds to the load, and defrost cycles. Flow temperature, radiator or duct sizing, and the electrical supply are separate design steps. In England, Approved Document L sets the efficiency standards for new work, and other countries have their own rules.

Using it with the rest of BuildMetricLab

Pair this estimate with the solar water heating, annual yield and EV charging calculators to plan the wider energy picture. Every BuildMetricLab tool runs entirely in your browser, with no sign-up. Nothing you type is sent to a server, and the formula is shown on the page so the maths can be audited.

Sources & methodology

Heat loss in kW = heated volume × heat-loss factor × design temperature difference ÷ 1,000, where volume is floor area × ceiling height. The factor is 1.5, 1.0, 0.6 or 0.35 W per m³ per °C for poor, average, good or passive fabric; these are rule-of-thumb values, not measured data for your building. The page takes area in ft², height in ft and the temperature difference in °F, and converts them (1 ft² = 0.0929 m², 1 ft = 0.3048 m, a difference of 1 °F = 0.5556 °C), so both unit systems agree. The result is shown as the indicative heat pump size in kW, and also in BTU/h (1 kW = 3,412.14 BTU/h) and tons (12,000 BTU/h). The area, height and temperature difference must be above zero. The tool sizes the heat requirement only. It does not model capacity at low outdoor temperature, defrost, hot water, ventilation losses by room, or oversizing, and a room-by-room calculation replaces it.

Frequently asked questions

Is this an ACCA Manual J heat-loss calculation?

No. It is a whole-building rule of thumb for sanity-checking a quote. A full room-by-room ACCA Manual J load calculation is the design standard in the US, and ENERGY STAR advises that your contractor verifies the size with it. Its answer can differ significantly from this estimate.

What design temperature difference should I use?

It is the indoor target temperature minus the coldest outdoor design temperature for your location, as a difference. A mild climate may give about 20 to 25 °C (36 to 45 °F). A cold northern climate can give 35 to 40 °C (63 to 72 °F). For 70 °F inside and a design temperature of 27 °F, the difference is 43 °F. Ask your contractor for your local design temperature.

Why does the fabric standard matter so much?

Heat loss scales directly with the fabric factor. The factors are 1.5, 1.0, 0.6 and 0.35 W per m³ per °C for poor, average, good and passive. So a good building needs 40% of the heat of a poor one of the same size, and a passive one about 23%. The default 5.2 kW for a 216 m³ home falls to 3.1 kW at good and 1.8 kW at passive.

Does this set the flow temperature?

No. Flow temperatures, radiator or duct sizing, hot water, and the electrical supply are design decisions for a qualified HVAC contractor, and are not part of this estimate. Heat pump output also falls as the outdoor temperature drops, so check the model's rated output at your design temperature.

Spotted something off?

Calculations or display — let us know.